摘要:
分析了一次回风加再热系统、二次回风系统及温度湿度独立控制系统的空气处理过程,以浙江省某市级中心医院的一间 Ⅰ 级和一间 Ⅱ 级洁净手术室为例,计算了这3个方案空气热湿处理过程中的耗电量,得出采用温度湿度独立控制空调系统以高温冷水机组供冷的方案最节能。
关键词:建筑节能,温度湿度独立控制,手术室净化空调,能耗,高温冷水机组
Abstract:
Analyses the heat and humidity controlling process for the primary return air plus reheat system, secondary return air system and temperature and humidity independent processed air conditioning system. Taking a classⅠ and a class Ⅱ clean operating rooms for example, calculates the electric power consumption for the three schemes. The results show that the temperature and humidity independent processed air conditioning system which uses high temperature cooling water as cooling source is the most energy efficient scheme.
Keywords:building energy efficiency, temperature and humidity independent processed, clean air conditioner of operating rooms, energy consumption, high cooling water temperature chiller