旋风喷雾油烟净化器的试验研究
Test on cooking smoke purification device with cyclone and spray
摘要:
利用湿法与离心分离法净化机理,研制出旋风喷雾油烟净化装置。试验结果表明,净化器内断面风速为1.8 m/s左右,洗涤液浓度为5%~7%,水气比为0.9~1.1 kg/m3时效果较优,净化效率可达80%以上, 最高可达92%。该装置结构紧凑、式样美观,适合用于饮食业的油烟净化。
关键词:油烟,旋风,喷雾,设备,复合法净化
Abstract:
Utilizing the purification mechanism of wet method and centrifugation, develops a set of cooking smoke purification device. The test results show that purification efficiency is nearly the best i.e. over 80%, even reaching 92% when the sectional air speed in the device is about 1.8 m/s, cleaning solution concentration is 5%, and spraying water amount is 0.9 to 1.1 kg/m3. It is compact in structure and good in appearance, suitable for the cooking smoke purification in catering services.
Keywords:cooking smoke, cyclone, spray, device, compound purification