暖通空调>期刊目次>2012年>第8期

燃气冷热电三联供与地源热泵的联合应用

Application of combined cooling heating and power and ground-source heat pump systems

王明友[1],程新红[1],黄艳[1],杨智勇[1],李炳华[1],许伟明[2],刘万添[3]
[1]中建(北京)国际设计咨询有限公司,[2]北京建筑工程学院,[3]北京中竞同创能源环境技术有限公司

摘要:

以中新天津生态城能源站为例,分析了联合系统一次能源效率、燃料节约率、经济性、影响因素的敏感性和环保性等,结果表明,冷热电三联供系统的能源利用率可达88.9%,联合系统的能源消耗比常规系统少18.5%,冷热电三联供系统的初投资在6年内可以收回。

关键词:中新天津生态城,冷热电三联供系统,地源热泵,运行模式,能源站,能源效率

Abstract:

Taking the energy station of the Sino-Singapore Tianjin Eco-city as an example, analyses the primary energy efficiency, fuel saving rate, economical efficiency, sensitivity of influence factors and environmental performance of the combined system. The results indicate that the energy utilization rate of the cooling heating and power system can reach to 88.9%, the energy consumption rate of the combined system is 18.5% less than the conventional system and the initial investment of the cooling heating and power system can be recovered within six years.

Keywords:Sino-Singapore Tianjin Eco-city, cooling heating and power system, ground-source heat pump, energy station, energy efficiency

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!