燃气冷热电三联供与地源热泵的联合应用
Application of combined cooling heating and power and ground-source heat pump systems
摘要:
以中新天津生态城能源站为例,分析了联合系统一次能源效率、燃料节约率、经济性、影响因素的敏感性和环保性等,结果表明,冷热电三联供系统的能源利用率可达88.9%,联合系统的能源消耗比常规系统少18.5%,冷热电三联供系统的初投资在6年内可以收回。
关键词:中新天津生态城,冷热电三联供系统,地源热泵,运行模式,能源站,能源效率
Abstract:
Taking the energy station of the Sino-Singapore Tianjin Eco-city as an example, analyses the primary energy efficiency, fuel saving rate, economical efficiency, sensitivity of influence factors and environmental performance of the combined system. The results indicate that the energy utilization rate of the cooling heating and power system can reach to 88.9%, the energy consumption rate of the combined system is 18.5% less than the conventional system and the initial investment of the cooling heating and power system can be recovered within six years.
Keywords:Sino-Singapore Tianjin Eco-city, cooling heating and power system, ground-source heat pump, energy station, energy efficiency