暖通空调>期刊目次>2006年>第12期

生物安全实验室气流组织效果的数值模拟研究

Numerical simulation study on air distribution effects in biosafety laboratories

曹国庆[1],张益昭[1],许钟麟[1],于玺华[2],温风[1],刘华[1],赵力[1],冯昕[1],赵辉[1],姚丹[1]
[1]中国建筑科学研究院空气调节研究所,[2]中国人民解放军第302医院

摘要:

对上送上排和上送下排气流组织形式下生物安全实验室内的污染物浓度场和气流速度场进行了数值模拟,结果表明上送下排在室内污染物排除效果上明显优于上送上排。将数值模拟结果与模型实验结果进行了对比,二者基本一致。

关键词:生物安全实验室,气流组织形式,数值模拟,上送上排,上送下排

Abstract:

Numerically simulates the concentration field of contamination and the velocity field of airflow in biosafety laboratories applying up-supply and opposite up-exhaust mode and up-supply and opposite down-exhaust mode. The results show that the latter mode is much better than the former one in contamination eliminating. Compares the numerical simulation results with those from a model experiment, and finds that they are in good agreement.

Keywords:biosafety laboratory, air distribution mode, numerical simulation, up-supply and up- exhaust, up-supply and down-exhaust
本站下载
镜像服务器下载