暖通空调>期刊目次>2007年>第11期

高层建筑加压送风防烟系统软、硬件部分可靠性分析

Reliability analysis on hardware and software elements for smoke control and pressurization ventilation system of high-rise buildings

刘朝贤
中国建筑西南设计研究院

摘要:

为了分析系统可靠性,将《高层民用建筑设计防火规范》(GB 50045—95)表8.3.2-1~4的4种加压送风防烟方案进行了简化。分析硬件部分的可靠性时,根据该规范规定的防烟技术条件,运用概率理论和可靠性原理推导并建立了加压送风防烟系统的可靠度计算数学模型,经过简化、推理分析,对不同方案的可靠度进行了比较。软件部分是防烟系统致命失效的重要原因,涉及加压送风防烟的许多原则问题,如加压送风量的计算方法、加压送风的最佳部位、加压送风口的形式及开启方式,以及笔者从实际工程调查中发现的加压送风系统保障体系等,对这些软件元素故障机理和对系统可靠性的影响等分别进行了分析。对系统硬件部分和软件部分可靠性分析的结论,可为加压送风防烟系统的优化和防烟规范条文的修订提供理论依据,供高层建筑防烟设计和研究人员参考。

关键词:可靠性 概率 计算方法 加压送风口 开启方式 保障体系

Abstract:

For analysing the reliability of hardware and software elements, simplifies the four smoke control modes in Tables 8.3.2-1 to 4 of the Code for fire protection design of tall buildings. For hardware reliability analyses, develops a reliability calculation mathematic model on smoke control and pressurization ventilation system according to the technical conditions of smoke control system regulated by the Code, statistics theory and reliability principle. Compares the reliability of different mathematic models based on simplification and reasoning. As important factors of fatal failure in smoke control system, software elements involve some essential problems, including the calculation method of air rate for pressurization ventilation, the optimal position of the air outlet, the form of air outlet and opening mode, and especially the guarantee system of pressurization ventilation system put forward by the author from actual project investigation. Analyses respectively the failure mechanism of software elements and their influence on system reliability. The analysis result provides theoretic references for the optimization of pressurization ventilation system, code revision, and smoke control system design and research of high-rise buildings.

Keywords:reliability, probability, calculation method, pressurization inlet, opening mode, guarantee system

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!