五星级酒店复合式水蓄冷系统的设计及应用
Complex chilled water storage system design and application for a five-star hotel
摘要:
以某五星级酒店冷源中心为例,介绍了一种复合式水蓄冷系统全年供冷热的设计方法。阐述了间接蓄冷-直接供冷水蓄冷系统的可行性及相应特点。详细介绍了布水器的计算方法,并给出相应的推荐参数设置值。结合常规空调系统进行了经济性分析和比较。基于目前水蓄冷运行现状,提出自控系统的重要性。
关键词:五星级酒店,复合式水蓄冷,布水器,经济性分析,自控
Abstract:
Taking the cold source center in the five-star hotel as an example, states the design method of complex chilled water storage system throughout the whole year. Discusses the feasibility and characteristics of indirect charging and direct discharging system. Expounds the calculation method of water distributor in detail and gives the recommended parameter settings. Makes the economic analysis and comparison combined with the normal air conditioning system. Based on the current status, points out the importance of building automatic control system.
Keywords:five-star hotel, complex chilled water storage, water distributor, economic analysis, automatic control