江水直供与热泵联合驱动的溶液调湿空调系统节能性分析
Energy efficiency analysis for liquid desiccant air conditioning system driven by river water and heat pump
摘要:
高温冷源是影响溶液调湿温度湿度独立控制系统节能性的关键因素。以实际项目为例,针对项目周边江水水温逐时数据,分析了由江水直接作为系统高温冷源的可行性,计算得到江水直供与热泵联合驱动的溶液调湿空调系统的节能率为20.52%。
关键词:温度湿度独立控制,溶液调湿,江水直供,水源热泵,节能性分析
Abstract:
High-temperature cold source is a key factor that influences energy efficiency of liquid desiccant based temperature and humidity independent process air conditioning system. Taking an actual project as an example, according to the hourly data of the river water temperature around the project, analyses the feasibility using river water as the high-temperature cold source directly. Calculation results show that the energy saving rate of this system is 20.52%.
Keywords:temperature and humidity independent process, liquid desiccant, direct river water supply, water-source heat pump, energy efficiency analysis