冷藏库光伏发电集成蓄冷制冷系统能耗和节能性研究
Research on energy consumption and energy saving of refrigeration systems with photovoltaic power generation integrated cool storage in refrigerated warehouses
摘要:
基于峰谷分时电价机制,将光伏发电技术与蓄冷技术结合用于冷藏库的制冷系统,降低冷藏库能耗,实现电力负荷的削峰填谷以降低运行费用。运用TRNSYS软件建立了系统仿真模型,探究了冷藏库光伏发电集成蓄冷制冷系统的节能潜力。对于某230 t苹果冷藏库,光伏发电集成蓄冷制冷系统可降低月耗电量21.86%~30.65%,降低月运行费用46.13%~65.85%。
Abstract:
Based on the peak-valley time-of-use electricity price mechanism, photovoltaic power generation technology is integrated with cool storage technology for the refrigeration system of the refrigerated warehouse to reduce the energy consumption of the refrigerated warehouse and realize peak shaving and valley filling of the power load to reduce operating costs. A system simulation model is established using TRNSYS software to explore the energy-saving potential of the refrigeration system with photovoltaic power generation integrated cool storage for refrigerated warehouses. For a 230 t apple refrigerated warehouse, the refrigeration system with photovoltaic power generation integrated cool storage can reduce monthly power consumption by 21.86% to 30.65% and monthly operation costs by 46.13% to 68.31%.
Keywords:photovoltaic power generation; cool storage; refrigeration system; refrigerated warehouse; peak shaving and valley filling; energy saving