暖通空调>期刊目次>2024年>第5期

声波法在直埋供热管道泄漏检测中的工程应用

Engineering application of acoustic wave method in leakage detection of directly buried heating pipeline

郭帅杰[1][2] 张立申[3] 李成[1] 穆连波[1] 王随林[1] 鲁军辉[1]
[1]北京建筑大学,北京;[2]北京市煤气热力工程设计院有限公司,北京;[3]北京市热力集团有限责任公司,北京

摘要:

利用声波法对城市内2段直埋供热管道的泄漏情况进行非开挖式工程实测,分析了不同工程条件下的泄漏声波信号特征,并采用傅里叶滤波进行声波振动信号的降噪处理。研究表明,傅里叶滤波可有效提升泄漏定位精度,实测漏点定位误差小于2%,基于傅里叶滤波降噪的声波法直埋供热管道泄漏检测技术具有较好的工程应用价值。

关键词:供热管道;声波法;泄漏;检测;定位;直埋

Abstract:

In this paper, the acoustic wave method is used to measure the leakage of two sections of directly buried heating pipelines in the city by trenchless engineering. The characteristics of the leakage acoustic wave signal under different engineering conditions are analysed, and the acoustic wave vibration signal is denoised by Fourier filter. The research shows that Fourier filter can effectively improve the accuracy of leakage location, and the measured leakage location error is less than 2%. The acoustic wave method based on Fourier filter denoising has good engineering application value.

Keywords:heating pipeline; acoustic wave method; leakage; detection; localization; direct burying