暖通空调>期刊目次>2009年>第7期

西安市公共建筑夏季空调能耗调查与温湿度实时测试分析

Survey on energy consumption status and field test of temperature and humidity for public buildings in Xi’an in summer

王燕[1],李安桂[1],师树海[2],王智超[1]
[1]西安建筑科技大学,[2]西安市城乡建设委员会

摘要:

2008年8月对西安市15栋公共建筑进行了能耗调研与分析,并对室内温湿度进行了为期5天每天24 h的连续监测,得出了西安市的公共建筑单位面积能耗指标为0.55~2.96 GJ/(m2·a),平均值为1.29 GJ/(m2·a),其中单位建筑面积空调能耗为0.20~1.97 GJ/(m2·a),平均值为0.70 GJ/(m2·a),并与北京、上海、天津、广州等城市能耗状况进行了对比分析,提出了空调系统存在的问题以及节能措施。

关键词:公共建筑 能耗 节能 调查

Abstract:

Investigates and analyses energy consumption of fifteen public buildings in Xi’an in August 2008, monitors the indoor temperature and humidity for a period of five days around-the-clock, and obtains the mean energy consumption per unit building area from 0.55 to 2.96 GJ/(m2·a), averaged 1.29 GJ/(m2·a). Contrasts them with the data of Beijing, Shanghai and Guangzhou. Puts forward some problems existed in air conditioning system and some approaches for improving energy utilization.

Keywords:publicbuilding,energyconsumption,energyconservation,survey

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!