空调用制冷机能耗分析
Energy consumption analysis of refrigerating machines used for air conditioning
摘要:
指出了制冷机能耗分析中存在的不足,提出了新的分析思路,并以实验用空调制冷机为例,对制冷机的制冷剂循环、冷却水循环、冷水循环能耗进行了计算分析,结果表明,在制冷机总能耗中制冷剂循环占22%,冷却水循环占7%,冷水循环占71%。
关键词:能耗,分析,实验用空调制冷机
Abstract:
Points out deficiencies in some energy consumption analysis of refrigerating machines. Taking experimental refrigerating machine used for air conditioning as an example, analyses and calculates energy consumption of refrigerant cycle, cooling water cycle and chilling water cycle. The results show that the energy consumption proportion of the three cycles is 22%, 7% and 71% respectively.
Keywords:energy consumption, analysis, experimental refrigerating machine for air conditioning