水煤浆热电联产集中供暖系统火用环境分析

Exergoenvironmental analysis of a combined heat and power system for district heating using coal water slurry

种道坤 周海珠 李晓萍 李以通
中国建筑科学研究院有限公司

摘要:

采用清洁燃料水煤浆的热电联产系统被视为传统燃煤系统的高效替代,目前缺乏针对此类系统环境性能的定量评价研究,且现有研究大多建立在仿真模型的基础上。本文以某实际运行的热电联产集中供暖系统为例,采用火用环境分析方法,对其热力学性能和环境学性能进行了量化评估。从系统和设备2个层面,确定了其性能水平和提升潜力。结果表明:该系统热力和电力的单位火用环境学影响值分别为5 434 mPts/GJ和3 617 mPts/GJ,环境学影响的主要来源为设备内部火用损失,改善措施主要为提高设备火用效率;水煤浆锅炉和汽水换热器具有较大的环境学性能提升潜力。

关键词:热电联产;集中供暖;火用环境分析;水煤浆;环境学性能;环境学影响;火用效率

Abstract:

The combined heat and power (CHP) system using clean fuel coal water slurry has been regarded as a high-efficiency alternative for conventional coal-fired district heating systems. However, there is a lack of quantitative evaluation of the environmental performance of such systems, and the previous research is mostly based on the simulation model. In this paper, taking an actual running CHP system for district heating as an example, the thermodynamic and environmental performances are quantitatively evaluated by means of exergoenvironmental analysis. From the two levels of system and equipment, the performance level and improvement potential are determined. The results show that the environmental impacts per unit exergy of thermal and the power of the system are 5 434 mPts/GJ and 3 617 mPts/GJ, respectively. The exergy destruction of system components is the dominant source of total environmental impacts, and the improvements in the environmental performance should focus on enhancing components’ exergy efficiency. The coal water slurry boiler and the steam-water heat exchanger have greater potential to improve environmental performance.

Keywords:combined heat and power; district heating; exergoenvironmental analysis; coal water slurry; environmental performance; environmental impact; exergy efficiency

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!