新冠灭活疫苗生产车间暖通空调系统浅析
Analysis of HVAC systems in COVID-19 inactivated vaccine production workshops
摘要:
结合建设经验及对相关规范的理解,介绍了新冠灭活疫苗生产车间中生物安全防护区暖通空调系统设计要点,从送排风系统、气流组织、压差梯度控制、空调自控等方面进行了详细阐述,建议新冠灭活疫苗生产车间空调通风系统送排风机均设置备用风机,防护区排风系统采用双级原位检漏过滤装置,并考虑定向气流、风口位置等因素满足生物安全的要求,制定合适的定、变风量阀控制策略,满足防护区压力恒定及工况转换的要求。
Abstract:
Through the summary of the construction experience and understanding of the relevant specifications, this paper presents the key technical points of HVAC system in the biosafety protection zone in the COVID-19 inactivated vaccine production workshop and elaborates the design details from the aspects of air supply system, exhaust system, air distribution, pressure gradient control, air conditioning auto-control system and so on. It is suggested that the standby fans should be arranged for air supply fans and exhaust fans in HVAC system of the workshop and the two-stage in-situ leak detection and filtration device should be adopted in the exhaust system in the protection zone. The directional air flow, air inlet or outlet location and other factors should be considered to meet the requirements of biological safety. Appropriate control strategies for constant and variable air volume valves should be formulated to meet the requirements of constant pressure and working condition conversion in the protection zone.