我的订单 | 我的收藏 | 加入收藏 | 返回首页
暖通空调>期刊目次>2021年>第11期

基于高效制冷机房系统能效分级评价的冷源系统模型构建

Construction of cold source system model based on energy efficiency grading assessment of high-efficiency chiller plant systems

谭海阳 屈国伦 何恒钊 黄冬娜 姜少华 林 辉 李 翔
广州市设计院集团有限公司

摘要:

基于制冷机房系统评价分级需求,提出了系统冷负荷为1 583 kW(450 rt)和7 034 kW(2 000 rt)的大小2个系统模型。明确了模型中冷源系统形式,以及冷水机组、水泵、冷却塔各设备参数中影响系统能效的参数选型原则,包括冷水机组的COP、水阻力、水温、机型,水泵的扬程、效率,冷却塔的能效、变频、冷幅、变流量等的要求,确保了模型的合理建立。

关键词:高效制冷机房系统,能效,分级,评价,模型

Abstract:

Based on the energy efficiency grading assessment requirements of the chiller plant system, puts forward two system models with cooling load of 1 583 kW (450 rt) and 7 034 kW (2 000 rt). Defines the form of cold source system in the model and the selection principle of parameters affecting system energy efficiency in various equipment parameters of chillers, water pumps and cooling towers, which includes the requirements of the COP, water resistance, water temperature and type of chillers, the head and efficiency of water pumps, the energy efficiency, frequency conversion, cooling approach, variable flow rate of cooling towers, and so on, ensuring the reasonable establishment of the model.

Keywords:high-efficiencychillerplantsystem,energyefficiency,grading,assessment,model

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!