上海地区数据中心空调现状分析
Analysis of air conditioning status for data centers in Shanghai
摘要:
选取上海地区20个大型数据中心为研究对象,采用调研评估、数据分析的方式对各数据中心空调系统的现状和能耗进行了分析。结果表明,各数据中心空调系统的原有设计均存在提升空间,且95%的数据中心空调系统存在能耗较高现象,具有一定的优化空间和节能潜力。结合数据中心行业内文件或标准,根据各数据中心的实际情况,提出了一些空调系统的节能技术措施,并分析了这些措施的节能潜力。
Abstract:
Selecting 20 large-scale data centers in Shanghai as the research objects, analyses the present situation and energy consumption of each data center’s air conditioning system by means of investigation, evaluation and data analysis. The analysis results show that there are some problems in the original design of these air conditioning systems, and 95% of the data centers have high energy consumption, which has a certain optimization space and energy saving potential. Combining with the data center documents or standards and each data center’s actual situation, puts forward some energy saving technical measures for air conditioning systems and estimates their energy saving potential.
Keywords:airconditioningsystem,datacenter,energysavingtechnology,energyefficiency,investigation