过渡季节冷却塔辅助供热的理论分析与研究

Theoretical analysis on cooling tower auxiliary heating in transition seasons

文先太,梁彩华,张小松
东南大学

摘要:

建立了计算模型,分析了室外温度和水流量对冷却塔热工性能的影响,讨论了优化水气比。得出在室外空气温度10.5 ℃、相对湿度60%、冷却塔进水温度0℃情况下,冷却塔辅助供热量达到45 kW,满足室内供热的需求。提高冷却塔风机风量使其满足优化水气比时,在满足冷却塔辅助供热量为45 kW的前提下,最低允许室外空气温度可达到7.6℃。

关键词:冷却塔,辅助供热,优化水气比

Abstract:

Establishes a calculation model, analyses the influences of outdoor air temperature and water flow rate on the thermal performance of cooling tower, and discusses the optimized ratio of water to air. The results show that when outdoor air temperature is 10.5 ℃, relative humidity is 60%, and inlet water temperature is 0 ℃, the auxiliary heating capacity of cooling tower can reach to as high as 45 kW, which meets the demand of indoor heating. When improving the air flow rate of cooling tower to reach the optimized ratio of water to air, with meeting the condition of 45 kW heating capacity, the allowed minimum outdoor air temperature can be as low as 7.6 ℃.

Keywords:coolingtower,auxiliaryheating,optimizedratioofwatertoair