暖通空调>期刊目次>2020年>第12期

低温热源条件下直连供暖系统用户超压问题解决方案探讨

Solution to overpressure problem of terminal heating equipment in direct supply systems with low temperature heat source

柏 婧 张 杰 刘 沛
北京市建筑设计研究院有限公司

摘要:

探讨了在低温热源、直连供暖系统中解决用户供暖末端设备超压的方案。以某供暖建筑面积为33万m2的住宅区域供热工程为例,分析了在不同的输送系统、补水定压系统下用户供暖系统工作压力的变化。最终采用用户泵设置在回水的三级泵输送系统及控制精度高的大型水泵式定压装置,在直连供暖系统中解决了低温地面辐射供暖系统超压的问题。该解决途径可供系统超压不多的低温热源项目参考。

关键词:直连系统,低温热源,超压,三级泵系统,补水定压系统

Abstract:

Discusses the solution to the overpressure of users heating terminal equipment in the direct supply system with low temperature heat source. Taking a residential building heating project with total heating area of 330 000 m2 as an example, analyses the working pressure changes of the users heating system under different hydraulic transportation systems and water replenishing and pressure fixing systems. Finally, applies the three-stage pump delivery system with the user pump installed in return water pipeline and the highly accurate controlled pump pressure fixing device to solve the overpressure problem in low temperature floor radiant heating systems. This solution can be used as a reference for the similar system with low temperature heat source.

Keywords:direct supply system, low temperature heat source, overpressure, three-stage pump system, water replenishing and pressure fixing system

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!