暖通空调>期刊目次>2006年>第9期

某别墅地埋管地源热泵空调系统设计与测试分析

Design and test of the ground heat exchanger ground-source heat pump system for a villa

高桂芝[1],王桂娟[1],田继民[2]
[1]河北工程技术高等专科学校,[2]沧州市建筑设计研究院

摘要:

介绍了该别墅地埋管地源热泵空调系统中地埋管换热器的计算方法。给出了一组冬季和夏季的运行数据。数据表明,该空调系统的供热量、制冷量、性能系数等基本能达到设计指标,冬季的换热器吸热量略小于设计值,应考虑适当的余量。

关键词:地源热泵系统,别墅,测试,分析

Abstract:

Presents the calculating method of ground heat exchanger in the ground-source heat pump system. Represents the operating data in summer and winter of a year. As a result, the heating capacity, cooling capacity and COP of the system can meet the design conditions, and the heat charge capacity of the heat exchanger is slightly smaller than the design condition, and an appropriate allowance should be considered.

Keywords:ground-source heat pump system, villa, test, analysis