Novel air-source heat pump system with external heat source auxiliary heating
Wang Xianlin, Yu Bo, Peng Guangqian, Wang Xicheng, Wu Junhong,Che Wen, Wang Ruifeng, Yang Wei, Yang Xudong and Ma Rongjiang
2020.10.15
Air-source heat pump frequently defrosts at the condition of low temperature and high humidity, and cannot continue heating during defrosting, which resulting in poor indoor thermal comfort. Presents a novel air-source heat pump system with external heat source auxiliary heating. The experimental results show that at the operating condition of -7 ℃/-8 ℃ of outside wet and dry bulb temperature, the continual heating operation time is up to 594 min, 195% longer than that of the conventional system, and the supply air with temperature no lower than 38 ℃ is still provided during the defrosting, which greatly improves the comfort experience.