Closer look at chiller ratings
W. Ryan Geister and Mike Thompson,Philip Yu,Chris Hsieh and Jia Jing
2014.12.26
Analyses the application conditions of IPLV/NPLV, points out the defects of IPLV/NPLV being used as an efficiency evaluation standard. It does not accurately represent a chiller plant’s operating characteristics, it can be used to compare unloading characteristics of chillers only, and it can not be used for predicting the economic savings by adding variable-speed drives. Considers that high-load operating points are extremely important when looking at the real operating points of chillers, and to ensure optimal solutions economically and environmentally, it is important to use accurate energy analysis tools.