Experimental research on reducing top concentrated air supply ceiling area in model hematology ward: Part 3 of the series of research practice of national standard Technical code on clean nursing and
Ma Zhaoyong, Jiang Guoqing, Xu Zhonglin, Cao Guoqing, Pan Honghong and Wang Weiping
2019.08.30
Performs an experiment in a model hematology ward with an area of 9 m2 and a height of 2.5 m. The results show that the cleanliness can be reached class-5 (indoor particle concentration much lower than 3.5 particles/L) when each side of top concentrated air supply ceiling is 0.4 m longer than the bedside. Meanwhile, the air velocity at 0.4 m height of bed head is lower than 0.1 m/s, which is far below blowing feeling velocity of 0.12 m/s. In addition, this air supply model can save 1/3 to 2/3 energy than regular project.