Optimized peak heat source configuration for secondary network of renewable energy heating system
Chen Wei and Chen Jian
2019.06.21
Combined with the characteristics of geothermal heating system, adopts a heating mode of energy station plus terminal heat exchange station, with the medium-deep geothermal energy for essential heat load and the natural gas boiler for peak heating load. Based on the annual cost method, develops a model aiming at minimal annual operating cost and annual life cycle cost. Taking a new district in Xian as an example, analyses the energy consumption, initial investment and annual operating costs with different peak heat load factors. The results show that the optimal peak heat load factor is 0.25.