Application of evaporative cooling water chillers to central refrigeration station of Karamay Cultural and Sports Center
Nie Yong, Sun Guocheng, Miao Xingchong and Zhang Yajun
The evaporative cooling water chillers are applied to the project of Karamay Cultural and Sports Center. Elaborates the project profile and temperature and humidity independent processed air conditioning system, and compares its electricity consumption with the mechanical refrigeration. The comprehensive cooling performance coefficient is 10.75. Compared with the same cooling capacity of mechanical refrigeration, the hourly electricity consumption decreases by 1 672 kW·h, and the annual electricity consumption decreases by 1.589 million kW·h. Summarizes the design problems in this project, and provides the references for the evaporative cooling air conditioning system application in dry areas.