Operational analysis on CCHP coulped with river water-source heat pump system in Chongqing
Shi Lijun, Rong Xiangyang, Si Pengfei, Min Xiaodan,Liu Mingfei, Hou Yubo and Yang Zhengwu
Combined with field measures and test data from third party, analyses the actual operational performance of a combined cooling heating and power system(CCHP)coupled with river water-source heat pump in Chongqing. The measure results show that power generating efficiency, exhaust heat recovery rate and primary energy ratio of CCHP are 35%, 52.7% and 82.3%, respectively. The cooling seasonal energy efficiency ratio and heating seasonal energy efficiency ratio of river water-source heat pump system are 3.85 and 3.97, when running at 55.6% of cooling load and 89.3% of heating load, respectively. Compared with actual operational strategy, the energy consumption can be decreased by 39.9% with design strategy.