Experimental study on static pressure reset method with linear adjustment of VAV air conditioning system suitable for online applications
Zhao Tianyi, Liu Chao and Zhang Jili
2017.11.23
Proposes a static pressure reset method based on maximum valve position terminal, and presents its structure and process. Tests and compares the fixed static pressure reset method, static pressure reset method with a fixed step value and static pressure reset method with linear adjustment in an integrated control experimental table for VAV air conditioning systems. The results show that the static pressure reset method with linear adjustment has better energy efficiency and control performance compared with other methods.