On-site measurement and analysis on operational energy performance of electricity-driven water-to-water heat pumps for centralized space heating systems
Wu Zhongjun, Wei Qingpeng, Deng Jiewen and Zhang Hui
2017.08.01
Presents the on-site measurement results of the operational energy performance of twenty-two heat pumps in fifteen centralized space heating systems in a city of northern China, including geothermal heat pump systems, sewage-source heat pump systems and seawater-source heat pump systems. The results show that the measured operational heating coefficients of performance are lower than the rated values for most heat pump units. Summarizes the typical problems existing in actual operation of heat pump units including low heat transfer performance by scaling of heat exchanger, low load ratio of heat pump units and super-high supply water temperature of end-user side.