Study on upper airflow velocity limit of cold compensation for sleeping human in hot environment

Zhu Minlin, Ouyang Qin, Zhu Yingxin and Shen Henggen

2017.06.20

Considers that thermal state of human body in supine posture position for a long time can simulate the thermal state before falling asleep. Carries out an experiment of long times lying-down to explore the upper airflow velocity limit of the cooling effect. Changes the temperature and humidity conditions in the experiment according to the tested peoples acceptability of hot environment, thermal feelings and fan states. When the temperature is 30 ℃ and the relative humidity is 70%, all the tested people accept the thermal environment, but feel hot and need to use the fan. Confirms the test duration for each condition by the stability time of thermal feeling under different ventilating conditions. The tested people who undergo four given airflow velocities vote for thermal feeling, thermal comfort, expected airflow velocity and the acceptable conditions. After analysing the relationship between the votes and the airflow velocities, the result shows that the upper limit of the airflow velocity for thermal neutral and thermal comfort during the sleeping is 1~1.2 m/s when the temperature is 30 ℃ and the relative humidity is 70%.