Parameter optimization and off-design operation strategy of multistage scroll heat pumps in heating station
Zhang Bin, Miao Qing, Tang Daoke and Fu Lin
Multistage scroll heat pumps can reduce the primary return water temperature to 15 ℃, and increase the heating capacity as well. In the three-stage structure of heat pumps with primary water temperature dropping equally, the total COP reaches maximum value of 5.62. While in the equal displacement mode which is easier for improving the design of the compressor, the total COP is 5.41, only declines by 3.7% compared to the maximum value. The experimental results show that the isentropic efficiency of the preliminary improved compressor is significantly higher than that of the prototype, but there is still room for further improvement. By means of quality regulation with the compressor starting and stopping control, the heating temperature can be kept within ±2.5 ℃ difference from the theoretical value, which can satisfy the heating demand of heat consumer.