Performance analysis of a novel ice slurry generation system
Hu Tao, Guan Haifeng, Dong Kaijun and Luo Weimin
2017.05.05
Designs a phase change and direct contact ice slurry generation system. Numerically simulates and studies the two theoretical slurry production systems of phase change and direct contact ice slurry generation system and conventional scraped surface ice slurry generation system under the same boundary conditions. The results show that the coefficient of performance (COP) of the novel system is 6.39, while conventional system is only 3.81, and the coefficient of ice producing performance (CIPP) increases 67.1% compared to the conventional system.