Performance analysis of water-loop heat pump combined with thermosyphon in buildings without interior zone

Nan Shuo, Li Xianting, Kong Qiongxiang, Shi Wenxing and Wang Baolong

2017.03.13

Water-loop heat pump (WLHP) system is evaluated as one of the most efficient air conditioning systems in buildings with large interior zone. However, WLHP has be applied to buildings with little interior zone in recent years because of its individual control and metering advantages. In winter the heat is mainly added to the water loop from boiler, which leads to the energy quality loss and operation cost of fuel and electricity. To solve this problem, proposes an integrated water-loop heat pump unit combining with thermosyphon and vapor compression refrigeration, which supplies heat from high temperature hot water to terminals directly with thermosyphon cycle. Taking a representative building without interior zone as an example, analyses the annual performance of the integrated WLHP applied in different climates based on simulation. The results show that the integrated WLHP has a great energy saving potential and applicability with its energy saving rate up to 30%~35% during heating period compared with conventional WLHP.