Experimental study on energy saving scheme of class Ⅱ clean operating rooms
Feng Peibing and Zhang Zhiqiang
2014.12.18
By adopting the patent results such as bacteriostatic type energy saving air conditioner, ultra low resistance fresh air filtration section and prefabricated envelope, verifies the feasibility of reducing the air change rate of class II clean operating room to be 24 h-1. The experimental results show that the energy saving scheme can save energy by 50% than conventional scheme.