Transient condition model of heat pump unit with screw compressor based on data fitting
Huang Guangqin, Lu Jun, Wang Liang, Chen Peng
2014.12.17
Presents a basic COP function considering the effect of load ratio in rated condition. Considering the influence of the water flow rate and the inlet temperature in the condenser and the water flow rate and the outlet temperature in the evaporator on the COP of heat pump unit, obtains the polynomial functions of the correction factors by fitting to amend the basic COP, and establishes a model of COP in transient conditions. It is indicated by validity test that this model has higher accuracy, and the error is -7.66% to 5.41% in cooling condition and -5.71% to 13.82% in heating condition.