Adaptability of active chilled beam with outdoor air dehumidification cooling system

Hu Hong

2016.01.11

According to the features of sensible heat treatment with outdoor air dehumidification cooling system, discusses the adaptability conditions of outdoor air dehumidification cooling system at the design parameters. Taking the active chilled beam with outdoor air dehumidification cooling system as example, analyses this kind of system used in guest room, office, meeting room and business center, and finds that the coil characteristics and water temperature and other factors could affect the level of outdoor air cooling and dehumidification in a certain range. Puts forward a new concept called the ratio of moisture load and outdoor air volume. Concludes that the active chilled beam with outdoor air dehumidification cooling system is more suitable for the place with the ratio of less than 4.92 g/m3 by calculation.