Energy saving evaluation of temperature and humidity independent control air conditioning system based on test
Fu Qiang, Hu Zhenjie, Duan Baodong and Tian Zhe
Simulates the temperature and humidity independent control air conditioning systems of two office buildings in south and north China by TRNSYS, respectively. Tests the actual operating condition of the two systems. Finds that there exits gap between the simulation and the actual energy efficiency for every part of the system. The actual energy saving rate for both the cold sources and the entire system is 10% lower than that of the simulation. Analyses the operating condition for every part of the system. The results show that energy saving advantage of the temperature and humidity independent control air conditioning systems is not obvious compared to the traditional system. The reason is that the design load and equipment selection is not appropriate. In addition, there is a lack of effective operational mode and adjustment measures. It is suggested to modify the design ideas and the control strategy.