Air conditioning condensate water system design
Shi Zhenyu
Air conditioning condensate water system is an important but often overlooked part of the air conditioning system, and the diameter is usually selected by empirical estimation. Describes the air conditioning condensate water system design, and focuses on the hydraulic calculation of the condensate horizontal tube. Through comparison of the empirical estimate and the theoretical value of the minimum slope 0.003 galvanized steel pipes, selects the appropriate design depth ratio so that the empirical estimate is close to the theoretical value. According to the hot dip galvanized steel pipes and plastic pipes, calculates the drainage capacity for each diameter of different slope. Finally, presents several air conditioning condensate water recycling technologies.