Energy saving from variable flow operation of a heating system with heat metering

Tian Yuchen and Tu Guangbei

2015.10.09

Presents the energy saving principle of a frequencycontrolled pump and points out the applicability of the law of similitude for centrifugal pumps and the conception of constant efficiency curves. By citing distribution piping loss curve, analyses the two commonly used control methods of constant pump head and constant remote circuit differential pressure and considers that control with a constant remote circuit differential pressure is the better.