Energy efficiency analysis between air cooling direct evaporative air conditioning and water cooling air conditioning solution for data centers

Wang Qianfang, Peng Shaohua and Ding Qigang

2014.12.16

By analysis and calculation of air cooling direct evaporative air conditioning solution and water cooling units plus terminal coil solution, thinks that the energy saving of air conditioning pattern lies in the air conditioning load and the geographic position of the data center. The air cooling solution has advantage in northern area. The water chilling solution has advantage for the giant data center (area larger than 8 000 m2 ). Air cooling solution has more advantage for large and middle size data centers.