Study of life cycle energy and resource consumption of air conditioning schemes for residential buildings

Li Zhaojian and Jiang Yi

2015.03.17

Taking a high-rise residential building as a case, calculates the raw material and resource consumption in producing process of the equipment for five kinds of air conditioning schemes mostly used in residential buildings, according to the conditions of weather and thermal performance of the buildings in Beijing and Shanghai. Analyses the life cycle energy consumption for three kinds of air conditioning schemes according to the investigation data of operating energy consumption of air conditioning in residential buildings. The research results show that the consumption in materials, energy and resources of split air conditioning scheme are the lowest in the five air conditioning schemes. The life cycle energy consumption of water-cooling central air conditioning scheme is 6.6 times of that of split air conditioning scheme for the building in Beijing. Both the life cycle energy consumption and the material consumption of air conditioning in residential buildings would be increased by times if central air conditioning schemes are applied to the residential buildings.