Energy efficiency concept application in air conditioning system design for a biological vaccine plant
Liu Han
According to the large energy consumption of the plant, the energy efficiency potential should be taped fully. Taking a project as an example, analyses the energy consumption of three kinds of air conditioning systems including the primary return air, secondary return air, and temperature and humidity independent processed air conditioning system, and determines the last one. Compares the advantages and disadvantages of winter cooling in three forms, and selects the mode with natural cooling unit. According to the winter climatic characteristics of the project location, adopts the solution circulation heat recovery system. Proves that in the design of biological vaccine plant, making full use of the existing energy efficiency technology and equipments can achieve a significant energy efficiency effect.