Impact of hydraulic balance methods on characteristics of motorized valves in air conditioning water system terminals

Huang Yiyun,Zhang Ling and Chen Guangming

2015.03.11

Analyses the impact of three kinds of hydraulic balance methods on actual working characteristics of motorized valves. Finds that when using static balancing valves and dynamic balancing valves, the adjusting performance of motorized valves cannot meet the control demand, and considers that the best hydraulic balance device to match motorized valves is pressure difference control valves.