Analysis of relative heat transfer coefficient of plate heat exchangers under variable flow conditions
Zheng Ruiyun , Jiang Yongcheng and Fang Xiumu
Simplifies the relative heat transfer coefficient formula of plate heat exchangers with only the thermal resistance of heat convection remained. Deduces the formula under variable flow conditions based on the general correlation formula of heat convection of plate heat exchangers and obtains the fitted formula with the software of Origin 8.0. Calculating result shows that the thermal resistance of the plate and fluid fouling causes less influence on the relative heat transfer coefficient formula, even this has a greater impact on the heat transfer coefficient. In the common range of flow rate variation, the error of the simplified formula is less than 4% and that of the fitted formula is less than 5%, meeting the requirement of engineering application.