Design and performance of ductless self-cleaning chemical cabinet
Zhang Bo, Zhang Pengyi, Wang Jinlong, Kim Jeonghyun, Zhang Kexin
2014.12.15
One of the main sources of air pollution in chemical and biological laboratories is the chemical pollutants released from reagent bottles. In order to improve the air quality in such locations, designs the ductless self-cleaning chemical cabinet adopting the air cleaning technology combined vacuum ultraviolet photo-catalytic and ozone catalytic decomposition. Determines the key parameters of the cleaning module based on the experimental data—the time for photo-catalytic reaction is 30 s, and the bed depth of the ozone decomposition unit is 3 cm. The test results show that the cleaning effect of the model machine can meet the requirement of the standard.