Energy consumption analysis of liquid desiccant air conditioning system for industrial buildings

Tang Yidan and Liu Xiaohua

2015.02.11

Based on the system design and theoretical analysis of conventional air conditioning system and liquid desiccant air conditioning system for an industrial building in Shenzhen, compares the energy consumption and the COP of the two kinds of systems. The results indicate that in the outdoor design condition in summer, the COP of the conventional air conditioning system is 2.94, while that of the liquid desiccant air conditioning system is 5.42, and that the lower the humidity ratio of outdoor air is, the better the performance of liquid desiccant air conditioning system is, verifying the advantage of liquid desiccant air conditioning systems in energy saving.