Numerical simulation of heat transfer between outdoor units of multi-connected split air conditioning systems and ambience

Zhang Jian , Wang Shugang, Zhang Tengfei, Daizo Takaoka, Ju Wenjuan

2015.02.10

Treating the fin-coil structure as porous medium, analyses the heat transfer between the outdoor units and the ambience by using CFD method. Validates the accuracy of CFD simulation in terms of velocity and temperature distribution obtained by a test. Analyses the intake temperature of outdoor units under different arrangement schemes by CFD method, and obtains the optimal scheme for three units in a line, which is that the minimum separation distance between neighboring units is 0.2 m, and a vertical wall shall be apart from the unit line at least 0.8 m.