Energy saving measurement and analysis of zone and time control system for heating systems
Mu Lianbo, Zhang Chunlei, Wang Bingnan, Zhang Di, Zhang Tiegang
2014.12.15
In the light of the current situation of special purpose public buildings still being heated as normal without occupancy, causing energy waste, reforms the heating system of an example project by adopting a zone and time control system. Tests the energy saving amount, total energy saving effect and influence of different control schemes on indoor temperature of the reformed system. The results show that the heating energy saving rate is 25.8%, the total energy saving rate of the boiler room is 8.7%, and the energy saving effect is remarkable.