Discussions on authority of a valve in fresh air handling units
Pan Yungang
2015.02.04
According to the annual climatic parameters in Beijing, selects an actual fresh air handling unit and studies the characteristics of cooling capacity with water flow rate for coils. Obtains a rational valve authority. As a result, a valve authority of 0.3 is satisfactory and is more economical in design pump head and transporting energy consumption compared with that of 0.5.