Experimental research in the condensation performance of three types of glassfiber composite air duct flange
Gong Hongwei, Li Wei, Liu Jinxiang
2015.02.04
Sums up and designs three kinds of glassfiber composite air duct flanges, Ftype, Ttype and Jtype, tests their temperature and air duct surface temperature of Jtype. Analyses the behavior of Jtype flange temperature changing with ambient temperature and air temperature in duct, presents the temperature distribution pattern of the air duct with Jtype flange. The results show that only Jtype flange can not produce condense water, it is much better than the F and Ttype flange.