Control strategy of outdoor air volume based on predicted steady room CO2 concentration

Yang Shizhong and Ren Qingchang

2014.12.15

Traditional control strategies can not satisfy the demands of multi-room indoor air quality and reducing outdoor air load fully in outdoor air volume control of variable air volume air conditioning systems. According to the control requirements of multi-room CO2 concentration, proposes a control strategy of outdoor air volume based on the online prediction of steady room CO2 concentration. Through the real-time prediction of steady CO2 concentration in each air conditioning room, takes the room with the highest CO2 concentration as detected room and controls its CO2 concentration to meet the set value, while the CO2 concentration in other rooms is less than the set value. Presents the theoretical basis and steps of on-line steady prediction. Compared with the outdoor air ratio correction control method, the proposed control strategy can reduce the outdoor air load effectively on the basis of meeting the requirements of multi-room CO2 concentration.