Simplified heat exchange model of fan coil in wet cooling conditions
Ling Fei and Yang Chunjie
2015.02.03
To solve the heat exchange calculation problem of the fan coil in the semi-centralized air conditioning system, through a wet-dry switching method, designs a heat transfer model of the fan coil for wet cooling conditions. Based on the energy balance and heat transfer principles, simplifies the heat transfer model in which the heat exchange capacity can be simply determined by the chilled water flow rate, temperature of supply chilled water, and flow rate and temperature of supply air as independent variables. By means of a fan coil unit simulation test, obtains the heat exchange curves in different conditions. The result shows a higher accuracy of model.