Discussions on characteristics of variablespeed pumps controlled by pressure difference
Huang Yiyun, Zhang Ling
2015.02.03
Deduces the simplified equations of head ratio and shaft power ratio of variablespeed chilled water pumps by introducing the conception of controlled pressure differential ratio β. Presents that β is the key factor to energy saving of variablespeed pumps by acquiring characteristics of variablespeed pump controlled by pressure differential with different β. Compares the β value of primary pump with that of secondary pump, and believes that the variablespeed primary pump is always better than variablespeed secondary pump in energy saving in the same condition.